Soil Resistivity Evaluation and Grounding System Resistance

Soil Resistivity Evaluation and Grounding System Resistance

Copyright: © 2018 |Pages: 37
DOI: 10.4018/978-1-5225-3853-0.ch001
OnDemand PDF Download:
$30.00
List Price: $37.50

Abstract

This chapter contains the factors affecting the soil resistivity and grounding resistance such as the soil moisture content, soil mineral content and soil temperature. It discusses the methods of measuring of soil resistivity and grounding resistance using Wenner method. Method to obtain the required samples for obtaining accurate site resistivity is presented. Soil resistivity measurement procedure is given in this chapter. The chapter contains three electrode method or fall-of-Potential method, dead earth method, and ground resistance testing existing systems using ‘Selective' Clamp-on-Measuring of high voltage transmission towers feet resistance. Methods of calculating the apparent soil resistivity of Multi-Layers, apparent soil resistivity of two layers and apparent soil resistivity of three layers are presented in this chapter.
Chapter Preview
Top

Introduction

To design the most efficient and economical grounding systems for electrical networks and substations, it is necessary to obtain accurate values of the soil resistivity on the site. The soil at the most sites is non-uniform. The first part of this chapter includes different methods of soil resistivity measurements and methods used to compute the apparent resistivity of multi-layer soil structure and comparing the calculated values with the actual measurements. Also, the factors affecting the apparent soil resistivity of multilayer soil are investigated. Such these factors are:

  • 1.

    The number of layers of soil structure (double and three layers are considered in this chapter) and their arrangement.

  • 2.

    The thickness of each layer.

  • 3.

    The reflection factor between each layer.

Top

Factors Affecting The Soil Resistivity And Grounding Resistance

As it is known Grounding and bonding are integral part of any modern electrical protection system design. An effective, low-impedance ground system is a key element of this system. It is crucial in ensuring personnel safety, as well as providing reliable protection for vital equipment and to minimize interruptions of service and costly downtime. As shown in (Figure 1), the grounding system consists of three basic components: 1-grounding conductor, 2-the connection/bonding of the conductor to the grounding electrode and 3- the electrode itself

Figure 1.

Elements of simple grounding

The resistance of the grounding system has three basic components as follows:

  • 1.

    The resistance of the grounding electrode itself and the connections to the electrode. This resistance can be ignored for its very low value in case of using electrodes and cable connections having high conductivity.

  • 2.

    The contact resistance of the surrounding earth to the electrode, this resistance can also be neglected in case of making good contact between the grounding electrodes and the surrounding medium.

  • 3.

    The resistance of the surrounding body of earth around the ground electrode. This resistance represents the actual value of grounding resistance and it is proportional with the soil resistivity and affected by grounding system configuration.

Many factors, both natural and human, affect the grounding resistance of electrical networks. Some of these factors are:

Soil Moisture

The samples of soil, when thoroughly dried, may in fact become very good insulators having a resistivity in excess of 109 ohm-centimeters. The resistivity of the soil sample is investigated by Engineering Standards Branch and Telecommunications Standards Division (ESBTSD). (1994). as given in Table 1 and (Figure 2) the soil resistivity decreases rapidly as the moisture content increases from very little moisture to approximately 30 percent.

Table 1.
Effect of moisture content on soil resistivity
Moisture Content % by WeightResistivity Ω cm Top SoilResistivity Ω cm Sandy Loam
0More than 109 ohm-centimetersMore than 109 ohm-centimeters
2.5250000150000
516500043000
1053000185000
151900010000
20120006300
3064004200
Morane gravel300040 to 10000
Ridge gravel150003000 to 30000
Solid granite2500010000 to 50000
Figure 2.

Effect of moisture content on soil resistivity